A conductor thermal model related to CIGRE and IEEE solutions was developed and compared with measurements. Two pylons of a single line were equipped with weather monitoring stations and conductor temperature sensors based on Surface Acoustic Wave (SAW) principle. Also a fiber optic distributed temperature sensing system was installed to provide additional data. Over 2.5 million data points were evaluated. Developed model deviation for more than 99 % of values proved to be ±1 • C for SAW sensor and ±3.5 • C for the fiber optic measurement. Several ampacity determination methods were described from a transmission grid operator's point of view. Their features were compared in order to show at which planning period they could be useful. A new method for dynamic line rating determination was proposed. Although it reduces maximum ampacity gain, its advantage lies in minimizing measurement systems while retaining relatively stable value and low risk of temperature limit exceeding.
This paper deals with the undesirable effects arising in buried pipelines located in the vicinity of transmission lines. In particular, influence of electromagnetic fields from transmission lines to nearby buried pipelines by numerical methods is there solved. Further attention is paid to possible elimination of arising undesirable effects.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.