“…Despite the large progress in physical arc modeling [9], black-box models are still used to simulate dynamic arc network interactions due to their low calculation effort [10], [11]. A black-box model is a valuable tool to simulate a dynamic arc in ac or HVdc CBs because the analysis of the current that flows through and the voltage across the electric arc during the period that the current crosses zero gives insight to the CB's ability to handle the interruption of a fault current adequately [12].…”
Section: B Simulation Of Self-oscillation Circuitmentioning
confidence: 99%
“…Despite the large progress in physical arc modeling [9], black-box models are still used to simulate dynamic arc network interactions due to their low calculation effort [10], [11]. A black-box model is a valuable tool to simulate a dynamic arc in ac or HVdc CBs because the analysis of the current that flows through and the voltage across the electric arc during the period that the current crosses zero gives insight to the CB's ability to handle the interruption of a fault current adequately [12].…”
Section: B Simulation Of Self-oscillation Circuitmentioning
confidence: 99%
“…The interruption tests and pressure measurement data suggest that for the successful interruption, the pressure increase in the HC at CZ should be high enough and the gas temperature in the upstream region should be low enough to secure the thermal and dielectric interruption capability [3].…”
Section: Slf Interruption Performance Indexmentioning
confidence: 99%
“…Series puffers can provide a maximum rating of 245 kV-40 kA-60 Hz/50 kA-50/60 Hz [1][2][3]. In circuit breakers of this class, short line fault (SLF) interruption (L90) is one of the most demanding duties.…”
Section: Introductionmentioning