Influence of the grid parameters during under voltage ride through (UVRT) testing

Abstract: Under-voltage ride through (UVRT) tests can be carried out on system test benches, most of them are equipped with a converter based grid simulator. This paper describes the control of the artificial grid impedance at the 4 MW test bench at CWD. Validation measurements with the commercial wind turbine E‑115 E2 show that the virtual impedance specification is sufficient to perform UVRT tests with different grid parameters. Comparative measurements between the voltage divider based FRT Container and the grid simu… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1
1

Citation Types

2
11
0

Year Published

2022
2022
2024
2024

Publication Types

Select...
4
2

Relationship

2
4

Authors

Journals

citations
Cited by 8 publications
(13 citation statements)
references
References 11 publications
2
11
0
Order By: Relevance
“…However, the analysis in this paper also illustrated in detail that a limited accuracy or errors of the HiL systems, their simulation models, and controls could easily compromise the quality of the certification result. In the previous analysis in Section 5, we showed, for instance, that the UVRT results are sensitive to the correct emulation of the impedance by the PHiL, which correlates with the findings in [35], and that, for example, frequency control and synthetic inertia tests can easily be jeopardized by a MHiL system whose bandwidth is limited due to test bench restrictions and poor feedback signals.…”
Section: Discussionsupporting
confidence: 70%
See 2 more Smart Citations
“…However, the analysis in this paper also illustrated in detail that a limited accuracy or errors of the HiL systems, their simulation models, and controls could easily compromise the quality of the certification result. In the previous analysis in Section 5, we showed, for instance, that the UVRT results are sensitive to the correct emulation of the impedance by the PHiL, which correlates with the findings in [35], and that, for example, frequency control and synthetic inertia tests can easily be jeopardized by a MHiL system whose bandwidth is limited due to test bench restrictions and poor feedback signals.…”
Section: Discussionsupporting
confidence: 70%
“…In a former publication, we have already shown that the impedance control provides precise results in steady state operation [35]. This work investigates to what extent the PHiL setup allows an impedance replication in case of faulty grids, e.g., in case of under-voltage events.…”
Section: Impedance Control During Grid Faultmentioning
confidence: 98%
See 1 more Smart Citation
“…Both UPCC and IPCC are control feedbacks to follow the setpoints for internal source voltage U0 and virtual impedance Zk. The effectiveness of virtual impedance control is verified by measurements and presented in [36].…”
Section: Virtual Impedancementioning
confidence: 88%
“…Fig. 8 Virtual impedance control at the PCC [36]. a Control schematic, b Equivalent circuit vides a stiff grid with a natural SCR = 7.5.…”
Section: Natural Impedancementioning
confidence: 99%