2013 15th European Conference on Power Electronics and Applications (EPE) 2013
DOI: 10.1109/epe.2013.6634621
|View full text |Cite
|
Sign up to set email alerts
|

Control of grid-connected power converters based on a virtual admittance control loop

Abstract: The connection of electronic power converters to the electrical network is increasing mainly due to\ud massive integration of renewable energy systems. However, the electrical dynamic performance of\ud these converters does not match the behavior of the network, which is mainly formed by generation\ud facilities based on big synchronous generation systems. Depending on the desired electrical operation\ud mode different control structures can be implemented in the converters in order to get adapted with the\ud … Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
3
1
1

Citation Types

0
49
0
1

Year Published

2014
2014
2021
2021

Publication Types

Select...
8

Relationship

3
5

Authors

Journals

citations
Cited by 91 publications
(50 citation statements)
references
References 14 publications
0
49
0
1
Order By: Relevance
“…The admittance block is more feasible for the realistic implementation compared with the impedance block due to the absence of derivative term that is contained in the impedance block [27] and the simplicity in configuring the converter to be a current source rather than a voltage source. The resistance and inductance of the virtual admittance can be either set according to the predefined values or secondary control layer commands.…”
Section: Overall Control Schemementioning
confidence: 99%
“…The admittance block is more feasible for the realistic implementation compared with the impedance block due to the absence of derivative term that is contained in the impedance block [27] and the simplicity in configuring the converter to be a current source rather than a voltage source. The resistance and inductance of the virtual admittance can be either set according to the predefined values or secondary control layer commands.…”
Section: Overall Control Schemementioning
confidence: 99%
“…The overall control scheme of synchronous power controller the virtual admittance structure emulates the output impedance without leading to the difficulties in implementation. The main advantages lay on the effectiveness for the complete range of harmonic frequencies and the simplicity in the inner loop implementation [18].…”
Section: Overall Control Structurementioning
confidence: 99%
“…According to (18), the virtual reactance for each converter is set to the same per-unit value for a proportional load sharing.…”
Section: B Grid Disconnection and Island Operationmentioning
confidence: 99%
See 1 more Smart Citation
“…In most of these applications, the matter of inertia and different control methodologies for providing inertia is missing. Recently, several efforts have been carried out to perform virtual inertia with different control methodologies [22][23][24][25]. This virtual inertia is emulated by advanced control of power converters considering a short-term energy storage [25] which gave rise to the possibility of having a huge amount of converter-based components without comprising the system stability.…”
Section: Introductionmentioning