Growing penetrations of distributed photovoltaic (PV) generation in low-voltage electrical networks are raising new challenges for electricity industry operation. Voltage rise is a particular concern and new distributed voltage management techniques have been proposed in the literature. In this study, a novel distributed voltage control method is presented. The method is designed to be used by both PV systems and controllable loads and uses both a voltage and a power set point to manage control. These set points, along with a voltage sensitivity measure, are then used to control PV system generation and load-shedding. The objective of the control is to keep voltage levels within operational limits with reasonable accuracy. The method is practical; local measurements of net-power and voltage are used with no additional communication infrastructure required. The proposed method is compared to a power set point only and a voltage set point only control method. Results show the proposed method improves on both methods in terms of both voltage accuracy and the equity of intervention. Nomenclature C_PSP l,ph,h calculated active power curtailment (APC) for PV system located at 400 V line l, phase ph, household h according to power set point PSP l,ph C_VSP l,ph,h calculated APC for PV system located at 400 V line l, phase ph, household h according to voltage set point VSP l,ph,h DTx l distribution transformer (DTx) for 400 V line l PVout l,ph,h active power output from the PV system located at 400 V line l, phase ph, household h PSP l,ph power set point for all PV systems located on 400 V line l, phase ph. Pmes l,ph,h net-power (PV generation minus load) measured at household located at 400 V line l, phase ph, household h PV l,ph,h PV system located at 400 V line l, phase ph, household h S l,ph,h active power sensitivity at household located at 400 V line l, phase ph, household h VSP l,ph,h voltage set point for PV system located at 400 V line l, phase ph, household h Vmes l,ph,h voltage measured at household located at 400 V line l, phase ph, household h V ul upper voltage limit V_DTx_NL l no-load voltage for DTx connected to 400 V line l ΔV_DTx l