In this study, we study the water source heat pump and digital scroll compressor and experimentally in the multi-connected air-conditioning system. Variable performance is developed when the unit operates in refrigerating and heating mode. The maximum of refrigerating capacity is 36519.95W when inlet water temperature of the condenser is 30°C and dry-bulb temperature of indoor air is 32°C, at the same time the maximum of EER is 4.33 when inlet water temperature of the condenser is 20°C and dry-bulb temperature of indoor air is 27°C. The unit operates in heating mode, the maximum of heating capacity and EER is 33275.73W and 3.86 when inlet water temperature of the condenser is 30°C and dry-bulb temperature of indoor air is 20°C.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.