The paper proposes a design scheme of integrated supervisory control system which is suitable for both 110kV drytype transformer and intelligent substation. Some special problems such as how to measure temperature in the high voltage winding is discussed in the paper. Fiber grating sensor is used in the system because of its strong anti-interference ability and accuracy for temperature. The installation method, quantity and trace of fiber are also discussed. The grounded current of core and working current could be monitored through the high precision current transformer. The supervisory and control intelligent electronic device (IED) is used the modular design method based on high-performance ARM processor in order to improve the hardware and software efficiency. It receives the value of winding and core temperature, ambient temperature, grounded current, and analyzes the status of transformer. According to the data the IED could control the cooling fan to reduce the temperature. The IED also can deliver the data to substation control layer using IEC 61850. The comprehensive application server could display the panoramic data such as monitoring and warning data of transformer.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.