The performance of a novel impinging two-phase jet heat sink operating with single and multiple jets is presented and the influence of the following parameters is quantified: (i) thermal load applied on the heat sink and (ii) geometrical arrangement of the orifices (jets). The heat sink is part of a vapor compression cooling system equipped with an R-134a small-scale oil-free linear motor compressor. The evaporator and the expansion device are integrated into a single cooling unit. The expansion device can be a single orifice or an array of orifices responsible for the generation of two-phase jet(s) impinging on a surface where a concentrated heat load is applied. The analysis is based on the thermodynamic performance and steady-state heat transfer parameters associated with the impinging jet(s) for single and multiple orifice tests. The two-phase jet heat sink was capable of dissipating cooling loads of up to 160 W and 200 W from a 6.36 cm2 surface for single and multiple orifice configurations, respectively. For these cases, the temperature of the impingement surface was kept below 40 °C and the average heat transfer coefficient reached values between 14,000 and 16,000 W/(m2 K).
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.