Currently, Japanese grid codes require photovoltaic (PV) power generation systems to continue supplying power to the grid as soon as possible even if the systems temporarily stop their operation. Although the fault ridethrough capability was originally proposed for preventing a cascading frequency drop in the power system, the capability has the impact on other instability phenomena such as transient stability. In this study, we focus on the postfault active power recovery of the PV systems. The impact of the recovery speed on the transient stability is investigated under different load conditions, in particular static/dynamic load condition. Numerical examples are carried out for the one-machine one-load infinite-bus system, and the effects of the recovery speed are evaluated by equal area criterion and critical clearing time. As a result, we have found both desirable and undesirable effects on the transient stability depending on the load condition. C⃝ 2016 Wiley Periodicals, Inc. Electr Eng Jpn, 198(4): 26-36, 2017; Published online in Wiley Online Library (wileyonlinelibrary.com).
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.