This paper presents a study on the influence of the environmental factors (respectively, ambient temperature and solar radiation) on hot spot temperatures and the consumed and remaining lifetimes of power transformers. In this regard, 15 identical 105 MVA distribution transformers are considered, loaded with the same load, and operating in 15 areas of Romania (with different climatic characteristics). Using the equations recommended by IEC 60076-7 (modified in the case of the presence of solar radiation) the values of oil temperature, hot spot temperatures and consumed and remaining lifetimes in two days from July 2020 are calculated, both in the presence and in the absence of solar radiation. It is shown that the values of the hot spot temperature and of the consumed lifetimes differ from one locality to another and that they increase with the increase of the ambient temperature and the intensities of the solar radiation. Finally, it is shown that the results obtained can be used to develop more efficient maintenance programs for distribution power transformers.
We present a wide hand analysis of two types of resistive switches: series and parallel. In order to improve the RF parameters we have reduced the thickness of the substrate and placed the switches on different types of membranes.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.