This paper presents an active islanding detection method for a distributed resource (DR) unit which is coupled to a utility grid through a three-phase voltage-sourced converter (VSC). The method is based on injecting a negative-sequence current through the VSC controller and detecting and quantifying the corresponding negative-sequence voltage at the point of common coupling of the VSC by means of a unified three-phase signal processor (UTSP). UTSP is an enhanced phase-locked loop system which provides high degree of immunity to noise, and thus enable islanding detection based on injecting a small ( 3%) negative-sequence current. The negative-sequence current is injected by a negative-sequence controller which is adopted as the complementary of the conventional VSC current controller. Based on simulation studies in the PSCAD/EMTDC environment, performance of the islanding detection method under UL1741 anti-islanding test is evaluated, and its sensitivity to noise, grid short-circuit ratio, grid voltage imbalance, and deviations in the UL1741 test parameters are presented. The studies show that based on negative-sequence current injection of about 2% to 3%, islanding can be detected within 60 ms even for the worst case scenario.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.