2020
DOI: 10.1002/2050-7038.12560
|View full text |Cite
|
Sign up to set email alerts
|

Simulation and verification of thermal modelling to prevent from damages caused by the use of HH fuses

Abstract: Summary Several cases were reported, where high‐voltage high performance (HH) fuses exploded and damaged the surrounding switchgear. The root causes for these destructions were broken fuse elements damaged by cyclic thermal‐mechanical stress. The question arose how it will be possible to detect broken fuse elements while HH fuses are in operation at high voltage level. The access to the degrading HH fuse is especially not given in switchgear because of the presence of high voltage. An indicator for degrading f… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
1

Citation Types

0
1
0

Year Published

2020
2020
2023
2023

Publication Types

Select...
2
1

Relationship

1
2

Authors

Journals

citations
Cited by 3 publications
(1 citation statement)
references
References 2 publications
0
1
0
Order By: Relevance
“…For the detection of high rate of rise of the temperature due to broken fuse elements a temperature monitoring system based on an energy harvesting temperature measurement sensor was developed and patented. [7][8][9][10][11] F I G U R E 3 Switchgear with HH fuse and TOC sensor adapted Figure 7 shows the location of the thermocouple to measure the temperature distribution inside a gas insulated switchgear while the HH fuse has a single broken fuse element at phase b. Due to the broken fuse element the temperature increases rapidly inside the fuse tube whereas in the other fuse tube only a slight increasing of the temperature due to the normal heating can be detected.…”
Section: Measurments At Degenerated Hh Fusementioning
confidence: 99%
“…For the detection of high rate of rise of the temperature due to broken fuse elements a temperature monitoring system based on an energy harvesting temperature measurement sensor was developed and patented. [7][8][9][10][11] F I G U R E 3 Switchgear with HH fuse and TOC sensor adapted Figure 7 shows the location of the thermocouple to measure the temperature distribution inside a gas insulated switchgear while the HH fuse has a single broken fuse element at phase b. Due to the broken fuse element the temperature increases rapidly inside the fuse tube whereas in the other fuse tube only a slight increasing of the temperature due to the normal heating can be detected.…”
Section: Measurments At Degenerated Hh Fusementioning