Abstract:This article analyses the failure of a 500 mm-diameter cast iron (CI) water pipe that catastrophically fractured in Sydney in 2013. According to metallurgical analysis and finite element simulation, a longitudinal pre-existing crack initiated from the adjacent bell-joint and eventually propagated to a critical length in the pipe barrel over a certain period. There was evidence of leakage prior to the burst incident but information was inconclusive whether it was exactly from this pipe. Fatigue caused by cyclic… Show more
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.