Abstract:With the development of ultra-high voltage (UHV) technology, hybrid reactive power compensation (HRPC) will be widely applied in the future. To study the mechanism by which HRPC influences the characteristics of circuit breakers in UHV transmission lines, this paper establishes an improved electromagnetic coupling transmission line model for out-of-phase and short-line faults. Based on the HRPC equivalent model, a simulation analysis was performed on the characteristics of the circuit breaker when a fault occurs. Using an equivalent lumped parameter circuit, the rate-of-rise of recovery voltage (RRRV) computational formula was deduced and computed. The RRRV variation in the circuit breakers in the system, with and without HRPC, was obtained. Given the circuit breaker interruption characteristics, the research results provide an analysis foundation and a theoretical basis for optimizing the HRPC parameters and selecting the arrangements of circuit breakers in an UHV transmission line.