Faults analysis of lightning stroke-caused flashover in 220 kV double-circuit transmission lines on the same tower

Abstract: In this paper, four-phase simultaneous lightning stroke-caused faults have been analysed, which occurred in double-circuit transmission lines on the same tower. According to the fault patrol circumstance, lightning information data, fault recording imformation, ATP-EMTP transient simulation analysis, it can be determined that the four-phase flashover faults were caused by backflashover. The specific process was: lightning stroke top or ground line of 75# tower. The lightning current was shunted by the ground w… Show more