Evaluation of Methodology for Lightning Impulse Voltage Distribution over High-Voltage Windings of Inductive Voltage Transformers

Abstract: Knowledge of lightning impulse (LI) voltage distribution over transformer windings during the design stage of the transformer is very important. Specific design differences in inductive voltage transformers make the transient analysis approach different to the approach to the power transformers. In this paper, a methodology for acquiring lightning impulse voltage distribution over high-voltage (HV) winding of inductive voltage transformers is presented and evaluated. Resistance, inductance, and capacitance mat… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
1
1
1

Citation Types

0
2
0

Year Published

2022
2022
2024
2024

Publication Types

Select...
3
2

Relationship

0
5

Authors

Journals

citations
Cited by 5 publications
(4 citation statements)
references
References 32 publications
0
2
0
Order By: Relevance
“…The study of the transmission characteristics of the transformer is of great importance to the proposed voltage measurement method. The working principle of CVT is that it is equivalent to dividing the primary voltage through a capacitive voltage divider and then connecting it to a PT, which is more stable and has a smaller error [4][5]. The structure of CVT can be divided into two major parts: capacitor divider and electromagnetic unit, capacitor divider consists of high voltage capacitor L1 and medium voltage capacitor L2 in series, electromagnetic unit consists of intermediate transformer Z, compensation reactor Rc and its protection arrester R1, etc.…”
Section: Identifying the Transfer Characteristics Of Capacitive Volta...mentioning
confidence: 99%
“…The study of the transmission characteristics of the transformer is of great importance to the proposed voltage measurement method. The working principle of CVT is that it is equivalent to dividing the primary voltage through a capacitive voltage divider and then connecting it to a PT, which is more stable and has a smaller error [4][5]. The structure of CVT can be divided into two major parts: capacitor divider and electromagnetic unit, capacitor divider consists of high voltage capacitor L1 and medium voltage capacitor L2 in series, electromagnetic unit consists of intermediate transformer Z, compensation reactor Rc and its protection arrester R1, etc.…”
Section: Identifying the Transfer Characteristics Of Capacitive Volta...mentioning
confidence: 99%
“…One of the most important tests to consider is the LI test, which analyzes the transformers' capacity to hold transient overvoltage. Because of the disastrous impact that transient overvoltage can have on transformers-for example, an insulation breakdown-it is helpful and critical to have a precise simulation of the LI test available alongside the transformer design process [46,47]. This test is carried out with negative polarity standard lightning impulses.…”
Section: Transformer Dielectric Testsmentioning
confidence: 99%
“…Many scholars have therefore studied the problem of turn-to-turn short-circuit faults in dry-type voltage transformers. The authors of [6,7] employed the lightning shock test to diagnose the turn-to-turn insulation of voltage transformers. The authors of [8] used the partial discharge technique to test the insulation of solid-insulated electromagnetic voltage transformers.…”
Section: Introductionmentioning
confidence: 99%