Abstract:The distance relays of transmission lines find limitations in the presence of series compensated capacitor. One of them is the distance relay setting issue, in which either over-reach problem or under-reach problem may occur. To deal with this issue, a differential equation based adaptive distance relaying setting method for series compensated line is proposed. As for it do not need to identify whether SC/MOV is in fault loop, not need to know the parameters and the operating states of SC/MOV/GAP, and furtherm… Show more
Set email alert for when this publication receives citations?
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.