Capacitive Current Interruption With Air-Break High Voltage Disconnectors

Abstract: Abstract-Capacitive current interruption with air-break disconnectors in a high-voltage network is an interactive event between the circuit and arc with a variety of interruptions and reignitions. In this contribution, first, a theoretical analysis related to this interaction is presented. The effect of capacitances at the source side ( ) and load side ( ) is investigated. Three distinct frequencies are identified as contributing to the voltage and current events in the circuit. Besides the power frequency qua… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1
1

Citation Types

0
10
0

Year Published

2010
2010
2018
2018

Publication Types

Select...
3
2
1

Relationship

2
4

Authors

Journals

citations
Cited by 9 publications
(10 citation statements)
references
References 9 publications
(5 reference statements)
0
10
0
Order By: Relevance
“…The range of the highest re-ignition voltages is from 200kV-289kV (1.4-2.0 p.u), which is close to the maximum TRV. Also high reignition currents with values up to 531A in these tests are observed at high frequency when the capacitor banks at both sides equalize upon re-ignition [11]. After the re-ignition at t 3 , the arc extincts completely at the next current zero crossing and the interruption is successful.…”
Section: Successful Test Data Analysesmentioning
confidence: 66%
See 2 more Smart Citations
“…The range of the highest re-ignition voltages is from 200kV-289kV (1.4-2.0 p.u), which is close to the maximum TRV. Also high reignition currents with values up to 531A in these tests are observed at high frequency when the capacitor banks at both sides equalize upon re-ignition [11]. After the re-ignition at t 3 , the arc extincts completely at the next current zero crossing and the interruption is successful.…”
Section: Successful Test Data Analysesmentioning
confidence: 66%
“…The arc reignites again at this point. Due to the source and load side capacitors' charge equalization [11], a high-frequency current of 220A is observed (Fig. 4d), but overvoltages across load-and source side capacitors are not observed.…”
Section: A Analysis Electrical Signalsmentioning
confidence: 99%
See 1 more Smart Citation
“…Most of these conclusions can be explained from theoretical point of view [17], showing that with smaller C s /C l , transients in current and voltage are larger.…”
Section: Investigation Of Measured Datamentioning
confidence: 99%
“…As the HF and MF oscillations are damped out, the power frequency (PF) remains. A detailed theoretical analysis is given elsewhere [17].…”
Section: Brief Interruption Process Analysismentioning
confidence: 99%