This paper analyzes the single-phase auto-reclosing in optimized single-circuit transmission lines (O-TLs). Optimized transmission lines have the advantage of transmitting higher power in a narrower space. However, because of the strong capacitive coupling in O-TLs the single-phase reclosing can be compromised. Accordingly, this paper presents a comparison between single-phase reclosing in conventional lines and O-TLs. Four scenarios were tested: conventional neutral reactor, optimal value, typical value of 800 Ω, and the proposed alternative method, in which the response is close to the limit values of secondary arc current, and transient recovery voltage. Results show that the single-phase auto-reclosing is not compromised in nonconventional lines as long as higher neutral reactors are designed. Resumo: Este artigo apresenta uma análise do religamento monopolar em linhas de transmissão de circuito simples otimizadas (O-TLs). As linhas de transmissão otimizadas têm a vantagem de transmitir maior potência em uma faixa de servidão mais estreita, ou seja, com as fases mais próximas. Desta forma, devido ao forte acoplamento capacitivo nas O-TLs, o religamento monopolar pode ser comprometido. Nesse sentido, este artigo apresenta um estudo do religamento monopolar em linhas convencionais e nas O-TLs. Quatro cenários foram testados: reator de neutro convencional, reator com valorótimo, com valor típico de 800 Ω, e um método alternativo para especificação do reator em que os valores de corrente de arco secundário e tensão de restabelecimento transitória se aproximam dos valores limites estabelecidos em normas. Os resultados mostram que o religamento monopolar nãoé comprometido em linhas não convencionais desde que os reatores de neutros instalados sejam corretamente especificados, sendo seus valores superiores aos usualmente utilizados.