2017
DOI: 10.1109/tdei.2016.005913
|View full text |Cite
|
Sign up to set email alerts
|

Application of UHF sensors for PD measurement at power transformers

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1

Citation Types

0
71
0

Year Published

2017
2017
2023
2023

Publication Types

Select...
4
3
1

Relationship

1
7

Authors

Journals

citations
Cited by 104 publications
(73 citation statements)
references
References 4 publications
0
71
0
Order By: Relevance
“…E( f ): Electrical field strength at the antenna. As previous investigations [27] show, highest sensitivity for drain valve UHF sensors is achieved at a minimum insertion depth of d = 50 mm, which is used in this contribution (side note: The insertion depth d has to be the identical during both, the AF determination and the UHF measurement in the transformer). The known transfer function provided by the AF allows to incorporate the sensor into the calibration, which is transferring the point of calibration into the transformer.…”
Section: Calibration Methods For the Uhf Sensor (K 2 -Factor)mentioning
confidence: 99%
See 1 more Smart Citation
“…E( f ): Electrical field strength at the antenna. As previous investigations [27] show, highest sensitivity for drain valve UHF sensors is achieved at a minimum insertion depth of d = 50 mm, which is used in this contribution (side note: The insertion depth d has to be the identical during both, the AF determination and the UHF measurement in the transformer). The known transfer function provided by the AF allows to incorporate the sensor into the calibration, which is transferring the point of calibration into the transformer.…”
Section: Calibration Methods For the Uhf Sensor (K 2 -Factor)mentioning
confidence: 99%
“…Antenna factor (AF) of UHF drain valve[27]. Red: UHF sensor installed into the cell (direct mount,Figure 5a).…”
mentioning
confidence: 99%
“…This involves shutting off power supply for the device during connection/disconnection of probes which is a huge disadvantage [3]. Non-invasive methods include: acoustic emission [4,5], optical emission [6,7], electromagnetic or radio-frequency detection [8,9]. This paper concerns the use of invasive, classical method.…”
Section: Metrological Parameters Of the Measuring Systemmentioning
confidence: 99%
“…At present, the detection methods of PD of a power transformer mainly include electric measurements, ultrasonic method, optical method, and the ultrahigh‐frequency (UHF) method . UHF method has the advantages of strong resistance to onsite electromagnetic (EM) interference and high sensitivity and has been widely applied for the online monitoring of PD of power transformers .…”
Section: Introductionmentioning
confidence: 99%