Analysis of a Costly Fiberglass-Polyester Air Filter Fire

Abstract: In September 2020, a fire at a liquefied natural gas (LNG) plant in the Arctic areas of Norway received national attention. In an unengaged air intake, the heat exchanger designed to prevent ice damage during production mode, was supplied hot oil at 260 °C. In sunny weather, calm conditions, and 14 °C ambient temperature, overheating of the unengaged air intake filters (85% glass fiber and 15% polyester) was identified as a possible cause of ignition. Laboratory heating tests showed that the filter materials c… Show more