Modular multilevel converter based high voltage direct current (MMC-HVDC) transmission systems may increase the short-circuit current and affect the AC fault clearing of circuit breakers. To address this issue, this paper analyzes the influence of the MMC on the short-circuit current when a symmetrical or asymmetrical fault occurs in the AC system. Firstly, the influence mechanism of the MMC on the short-circuit current under symmetrical AC faults is studied. It is found that the short-circuit current magnitude at the fault point is mainly affected by the q-axis output current of the MMC. For the singlephase line-ground fault, the three-sequence equivalent circuit of the MMC is analyzed, and the calculation method of the three-sequence short-circuit current is presented. It is observed that the negative-and zerosequence currents at the valve side of the MMC are both zero, and the positive-sequence current is determined by MMC operating conditions. Besides, the short-circuit current magnitude under the singlephase line-ground fault is also mainly related to the q-axis output current of the MMC. Based on these results, an additional controller is proposed to reduce the short-circuit current under the symmetrical and asymmetrical faults. Finally, the effectiveness of the proposed mechanism and suppression control is verified by PSCAD/EMTDC simulations.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.