Ideally, it is desirable to design and manufacture a transformer winding that can render all its internal resonances nonexcitable. This study examines the effectiveness of an interleaved winding in achieving this goal. While investigating its effectiveness, it led to the establishment of a much desired theoretical basis that reinforces the reasons put forward in the literature to explain internal insulation failures observed in interleaved windings used in extra high voltage (EHV) transformers. Numerical calculations along with experimental verification on actual transformer windings are presented. This study reveals that most of the natural frequencies that are normally non-excitable in the line and neutral current responses of an interleaved winding have been rendered excitable in the disk-to-disk voltages, thus, providing favourable conditions for insulation overstress because of resonant overvoltages. Prevalence of such a condition is an inherent characteristic of interleaved windings.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.