Abstract. This paper designed and constructed a 126kV GIS partial discharge test platform, performed frequency breakdown tests and lighting impulse tests at temperature of -30~20 to SF 6 /N 2 gas mixture. The present experiment studied frequency breakdown tests in different temperatue and slightly inhomogeneous electric field, obtained change in frequency breakdown voltage as a function of temperature; Analysed positive and negative lightning impluse test in gas mixture, in which SF 6 had a propotion of 30%~60%, in different temperature. Results indicated 50% probability breakdown voltage variation in positive lightning impluse tests, and in a low temperature environment, the breakdown voltage increased at negative lightning impulse, the polarity effects varied with condition of pure SF 6 gas. The experimental results showed implement of SF 6 /N 2 mixed gas with 30% SF 6 supersedespure SF 6 gas, could effectively reduce the consume of SF 6 , and remit greenhouse efect.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.