In this study, the effects of various disk shapes of hydrant on the pressure drop are experimentally and numerically analyzed. The test methods for measuring pressure drop of hydrant are comply with standard of Underwriters Laboratory (UL). The hydrant as used in this study has one inlet, diameter 150 mm, and three outlet, 114.3 mm diameter for one outlet and 63.5 mm diameter for the others. The pressure of the hydrant are measured in the range 760 L/min~2,270 L/min for 63.5 mm outlet and 3,030 L/min~6,060 L/min for 114.3 mm outlet. Also, the numerical results of pressure drop are compared with the experiments to verify the accuracy and to analyze the of various valve shape of hydrant on the pressure drop. The engineering parameters, flow coefficients, are reduced from 181.57 to 136.35 (L/min/kPa 0.5 ) with inclined angle of disk from 0 o to 45 o . These results are able to practical use for design hydrant to minimize pressure drop.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.