The current 3-D numerical analysis explores the effect of combinations of rectangular winglet pairs (RWPs) having different attack angles (i.e. 5°, 15°and 25°) along a row of the tube array, on the performance of the fin and tube heat exchanger (FTHE). The considered airside Reynolds number Re ranges from 500 to 900. In total, six combinations of three attack angle vortex generators (VGs) have been numerically analysed namely 5°-15°-25°, 5°-25°-15°, 15°-5°-25°, 15°-25°-5°, 25°-5°-15°and 25°-15°-5°. The performance of the FTHE is represented by area goodness factor. The performance rankings of the FTHEs are also obtained by the MOORA method. Finally, 5°-25°-15°case provides the best thermal hydraulic performance for which heat transfer coefficient (h) is increased by 68.20% at Re = 500 and 81.78% at Re = 900, with a significant pressure drop penalty.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.