Abstract-The paper presents a fault location procedure for distribution networks based on the wavelet analysis of the fault-generated traveling waves. In particular, the proposed procedure implements the continuous wavelet analysis applied to the voltage waveforms recorded during the fault in correspondence of a network bus. In order to improve the wavelet analysis, an algorithm is proposed to build specific mother wavelets inferred from the fault-originated transient waveforms.The performance of the proposed algorithm are analyzed for the case of the IEEE 34-bus test distribution network and compared with those achieved by using the more traditional Morlet mother wavelet.
Among the innovative contributions to electric distribution systems, one of the most promising and qualified is the possibility to manage and control distributed generation. Therefore, the latest distribution management systems tend to incorporate optimization functions for the short-term scheduling of the various energy and control resources available in the network (e. g., embedded generators, reactive power compensators and transformers equipped with on-load tap changers). The short-term scheduling procedure adopted in the paper is composed by two stages: a day-ahead scheduler for the optimization of distributed resources production during the following day, an intra-day scheduler that every 15 min adjusts the scheduling in order to take into account the operation requirements and constraints of the distribution network. The intra-day scheduler solves a non-linear multi-objective optimization problem by iteratively applying a mixed-integer linear programming (MILP) algorithm. The linearization of the optimization function and the constraints is achieved by the use of sensitivity coefficients obtained from the results of a three-phase power flow calculation. The paper shows the application of the proposed approach to a medium-voltage 120 buses network with five wind plants, one photovoltaic field, ten dispatchable generators, and two transformers equipped with on-load tap changers
Abstract-The paper presents a procedure for fault location in distribution networks, based on the use of the integrated time-frequency wavelet decompositions of the voltage transients associated with the fault-originated travelling waves. The proposed analysis of time-frequency wavelet decompositions has been found to improve the identification accuracy of the frequencies associated to the characteristic patterns of a fault location with respect to a sole frequency-domain wavelet analysis. Several laboratory fault tests, carried out by means of a reduced-scale model of a distribution feeder, are used to illustrate the characteristics and assess the performances of the proposed improved procedure. The paper also illustrates the application of the proposed procedure to a transient, originated by a permanent phase-to-phase fault, measured in a real distribution network in which a post-test analysis has identified the faulted branch.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.