In this paper, the relationship between ventilation efficiency and air outlets ! return −intake systems in atrium space were analyzed by experimenta 監 studies and also by numerical simulation based Qn computational fluid dynamics ( CFD ) . The conclusions are as fbl 豆 ows ; 1. In the case ofcoGling and the occ 叩 ied zone be藍 ng limited the venti 且 ation efficiency has increased by arranging the supPly outlets at the 艮 ower part ofthe atr 孟 um . 2 , In the case ofavertical supply from the floor , a exhaust system at the ceihng is more desirable than tbat of the wall . 3. Effective arrangements fbr both the heat 重 ng and the coGhng modes are to supply the air from the wall at a height of 3500mm and exhaust
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.