Operating rooms are stringent controlled environments. All influential factors, in particular, airborne particles, must be within the limits established by regulations. Therefore, energy efficiency stays in the background, prioritizing safety and comfort in surgical areas. However, the potential of improvement in energy savings without compromising this safety is broad. This work presents a new procedure, based on calibrated simulations, that allows the identification of potential energy savings in an operating room, complying with current airborne particle standards. Dynamic energy and airborne particle models are developed and then simulated in TRNSYS and calibrated with GenOpt. The methodology is validated through experimental contrast with a real operating room of a hospital in Spain. A calibrated model with around 2% of error is achieved. The procedure determines the variation in particle concentration according to the flow rate of ventilation supplied and the occupancy of the operating room. In conclusion, energy savings up to 51% are possible, reducing ventilation by 50% while complying with airborne particles standards.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.