This study compared and analyzed the water treatment efficiency and the applicability of water treatment plant using the existing Mechanical Rapid-Mixer by introducing the Non-powered Vortex Mixer to the domestic water treatment plant. For this study, fluid flow characteristics and head loss of a Non-powered Vortex Mixer are calculated by Computational Fluid Dynamics (CFD)respectively. The head loss rate inside the mixer was 11.30% when the inflow velocity was 0.5 m/sec, 16.27% at 0.6 m/sec and 21.44% at 0.7 m/sec, the head loss rapidly increased at the optimal velocity of 0.5 m/sec. For the inflow velocity of 0.5 m/sec, the turbulent intensity at the inlet was 2.37% and at the outlet was 7.83%, so there was sufficient mixing strength for the particulate matter and the coagulant. The result of the water quality of the treatment plants with the inflow velocity of 0.38 m/sec that was operated in three years after replacing all 12 units of the existing Rapid-Mixer with the Non-powered Mixer met the standards. Hence, it is possible to reduce the energy consumption of 64,143 ~ 65,306 kWh/year since the Rapid-Mixer is replaced by the Non-powered Vortex Mixer.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.