Disconnector switching operations in large gasinsulated switchgear (GIS) systems may cause very fast transients oscillations (VFTO). These VFTO surges produce dielectric stress to other apparatus of the substation. This paper describes the test technique for measuring VFTO waves straight at the high voltage entry of a 550 kV/ 840 MVA generator stepup transformer. Additionally, the signal processing for elimination the test circuit transfer effect is explained. Repetitive tests identify the reliability of test circuit and test equipment. The characteristics of recorded VFTO impulses confirm the state-ofthe art experience of other publications.Different case studies are applied for identifying the worst case configuration of busbar system regarding the effective VFTO stress for the generator transformer. Operating the closest disconnector while all busbar systems are interconnected causes the highest dielectric stress for the transformer entry.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.