We study the dynamics of the motion of a metallic particle bouncing between alternating high-voltage electrodes in a compressed SF6 gas coaxial insulator. Through the study of the bifurcation diagram and attractors, we find that the dynamics of a metallic particle develops from a stable periodic motion to chaos as the strength of the electric field increases. Based on these results, we show numerically that the chaotic motion of the particle can be stabilized by using a chaos control method.
Frequency domain measurement of propagation loss for ultra high frequency (UHF) partial discharge in the winding of power transformer using a spectrum analyzer and pulse generator is presented. We compared the performance of the method using a network analyzer with and without a winding. Using a network analyzer simplifies the measurement and offers better dynamic range and frequency range. It also provides precise propagation loss within the winding in frequency domain at UHF range. We applied this method to measure UHF propagation loss of transformer mock-up, modeled 154 kV 20 MVA power in KEPCO substation.
In this paper, we studied the dielectric breakdown voltage characteristics by the AC withstand voltage test on using green insulation dry air instead of SF6 insulation gas used in the GIB (gas insulated bus) of 362 kV GIS (gas insulated switchgear). The AC withstand voltage test applied to the standard KEPCO's 362 kV GIB with dry air insulation, and the equivalence of dielectric breakdown voltage for dry air and SF6 gas were examined, and the empirical formulas of dielectric breakdown voltage for dry air were calculated, and the criterion of AC withstand voltage test for dry air insulation was derived. Using the criterion, dry air can be used instead of SF6 gas for 362 kV GIB in the factory acceptance test was confirmed.
This paper was provided to help in detecting defects in power transformer. For this purpose, a partial discharge cell was designed and manufactured as a discharge source to simulate particle defected paper-oil insulation in power transformer. Experimental set-up for measuring PD signals was described. Magnitude of electromagnetic wave signals and corresponding amount of apparent discharge were measured simultaneously against phase of applied voltage to the discharge cell. Frequency range and pattern of PRPD(Phase Resolved Partial Discharge) of partial discharge signals were examined and analyzed. The results will be contributed to build the defect database of power transformer and to decrease the substation faults.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.