In this article, the heat transfer, friction factor, and thermal performance factor characteristics of a concentric-tube heat exchanger are examined experimentally. A wavy inner pipe is mounted in the tube with the purpose of generating swirl flow that would help to increase the heat transfer rate of the tube. The examination is performed for a Reynolds number ranging from 2700 to 8800. An empirical correlation is also formulated to match with experimental data of the Nusselt number using the Wilson plot method. In addition, to obtain the real benefits in using the swirl generator at a constant pumping power, the thermal enhancement factor is also determined. Over the range considered, the increases in the Nusselt number, friction factor, and thermal performance factor are found to be, respectively, about 113 %, 81 %, and 196 % higher than those obtained from a smooth-surface inner pipe.Keywords Enhanced heat transfer · Heat exchanger · Wavy inner pipe · Wilson plot method
List of SymbolsA Area (m 2 ) d Diameter of wave (m) f Friction factor h Heat transfer coefficient (W · m 2 · K −1 )
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.