Inrush current is a transient phenomenon that occurs when a transformer is first energized to a voltage source at no-load conditions. It causes a very high inrush current. Inrush currents can adversely affect the electric power system and can cause improper work of a relay protection errors. The purpose of this study is to determine the amount of inrush current and minimize the amount of inrush current by using the pre-fluxing method.In this study, a test was carried out using a 3-kVA core type 3 phase transformer. This test is done by giving DC flux before the transformer is connected to the voltage source, then the three transformer phases are energized simultaneously at a certain voltage angle so that the inrush current may could be minimized. The test results show that the transformer that is given a DC flux always has a relatively small inrush current. In this test the inrush current is reduced to a minimum value at an ignition angle of 90 degrees with an inrush current value of 0.74 A in phase R, 3.41 A in phase S, and 3.80 A in phase T.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.