In this paper, the reliability of transients due to pump trip as a powerful tool for the pre-localization of anomalies in real pipe systems is tested. The examined pipe system is part of the one supplying the city of Milan, Italy and is managed by Metropolitana Milanese SpA (MM). The characteristics of such a system can be considered as intermediate between those of classical transmission mains and distribution systems because of its several branches. A Lagrangian model simulating pressure wave propagation is used to evaluate the pipe pressure wave speed -associated with a genetic algorithmand to locate possible anomalies -associated with wavelet analysis. The results of the diagnosis of the pipe system are corroborated by repairs executed by MM in the area where possible anomalies have been pre-localized.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.