The voltage sag performance of a distribution system has been investigated. A Monte-Carlo procedure has been used to construct the sag density table and estimate the number of unacceptable sags per annum at a sensitive load bus. The subtransmission lines and distribution feeders that largely contribute to the unacceptable sags have been identified. It has been shown that proper protective relay coordination and adequate maintenance of the critical lines and feeders result in significant improvement of the voltage sag performance of the distribution system.Index Terms-Monte-Carlo method, power quality, voltage sags.
Abstract.A location estimation system for online Partial Discharge (PD) detection is proposed as a low-cost approach to real-time condition monitoring, asset management and operation optimization in future smart grid. Some early progress in the development of subsystems (specifically the antenna, radiometer device, PD emulator and PD generator) for a proof-of-principle prototype system is described. The proposed PD Wireless Sensor Network (WSN) uses a novel approach to PD location which obviates the need for synchronization between sensors thereby improving scalability.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.