This article described the investigation of the failed superheater tube made of SA210 Grade C used in a biomass power plant. Visual inspection, microstructural examination, chemical analysis and hardness measurement were employed to analyze the causes of the superheater tube failure. Results from the investigation showed that the major cause of this failure was mainly related to the long-term overheating, resulting in the occurrence of the excessive thermal oxidation and graphitization. The excessive thermal degradation accelerated the reduction of the wall tube and promoted the build-up of the stress acting on the tube. Graphitization degraded the microstructure of the tube, reducing the mechanical performance of the tube. The combined effects from the severe thermal oxidation and graphitization attributed to the premature failure of the tube. It is therefore advised to use the correct material, SA213 T22, in the failed section. Material specification examination for superheater regions prior to tube installations should be performed to avoid the use of the inappropriate material. The temperature monitoring and mapping in this section were also suggested.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.