Heat exchanger is an equipment designed to exchange heat between two fluids by applying heat transfer by convection and conduction without mixing the two fluids. heat exchangers are used in the gold mining industry in the gold elution process stage with the type of alat penukar kalor pelat datar(PHE) UFX-42H to reheat the eluate (water) using glycol as the heating fluid. The PHE has a leak on the back base plate. This report aims to analyze the comparison of the effectiveness and LMTD of PHE between specification data and operational data at the time of leakage. The calculation off effectiveness requires the suhue, mass flow rate, and specific heat of the fluid. The results obtained were the effectiveness of the specification data is 0.83 and the mean of operational data is 0.71. The results of LMTD specification data is 23.91 and the mean of operational data is 28.1.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.