The creation of a measuring device for determining the impedance of the grounding of lightning arresters and supports of overhead lines under the influence of aperiodic pulses with the parameters 1.2/50 μs, 8/20 μs and 10/350 μs. Methodology. For this purpose, electrical engineering theory, transient modeling software and natural modeling methods are used. Results. The parameters of the electrical circuits of the additional forming unit were determined to create lightning current pulses with parameters of 10/350 μs using the IK-1U measuring complex. According to the simulation results, a layout of the forming unit in the form of an attachment and the IK-1U complex with the upgraded power supply system were created. Oscillograms of the front and pulse duration are obtained. The specified model was tested when performing electromagnetic diagnostics of the state of the RFP for more than 100 operating electrical substations. Originality. The measuring complex IK-1U was improved, which made it possible to determine the impulse impedance of the grounding device of lightning arresters when exposed to a current of 10/350 μs, 8/20 μs and of voltages 1.2/50 μs. Practical value. Upgraded device allows measurements in accordance with modern international requirements. References 9, tables 1, figures 3.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.