In an effort to increase electricity supply PT PLN (Persero) build GIS Tanah Lot in Nyitdah Village Tabanan regency. The new GIS development makes the network transmission system High Voltage Air Line 150 kV changed. Changes in this transmission system impact on the channel safety settings due to changes in transmission length and impedance value. Prior to the analysis of the impedance setting, the Distance Relay Distance Zone with current, working time and OCR Relay coordination (Over Current Relay) firstly analyzes short circuit flows two phases and three symmetric phases using ETAP PowerStation program. After calculation of distance relation setting, the value of channel impedance in Tanah Lot GIS is 2,4 + j 6,96 ? with Zone 1 setting (80%): 0,200 + j 0,588 ?, Zone 2 (120%): 0,30 + j 0.882 ?, and Zone 3 (220%): 0.68 + j 2.30 ?. OCR (Over Current Relay) release time setting is indicated by releasing delay (tD>) for Tanah Lot GIS - Antosari and Tanah Lot GIS - The vessel has a value of 0.48 with an actual working time release of 1.134 seconds.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.