In this work, three decentralized control configuration designs-independent, sequential and simultaneous designs-were used in multivariable feedback configurations for PI control of the riser and regenerator temperatures of FCCU in order to compare their performances. Control design was formulated as optimization problem to minimize infinity norm of weighted sensitivity functions subject to μ-interaction measure bound on diagonal complementary functions of the closed loop system. The optimization problem was solved using augmented Lagrangian genetic algorithm. Simulation results show that simultaneous and independent designs give good response with less overshoot and with no oscillation. Bound on μ-interaction measure is satisfied for both designs meaning that their nominal stabilities are guaranteed; however, it is marginal for simultaneous design. Simultaneous design outperforms independent design in term of robust performance while independent design gives the best performance in terms of robust stability. Sequential design gives the worst performance out of the three designs.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.