The use of distance relays in the system SUTT 150 kV network, is expected to help the reliability of the transmission system. Setting the value of the distance relay network systems SUTT 150 kV GI Kapal-GI Pemecutan kelod specified by PLN, to do research to obtain the new distance relay settings. Value setting relays within the network system SUTT 150 kV GI Kapal-GI Pemecutan kelod: Zone 1: (R = 0.977, X = 2.684, Z = 2.86), Zone 2: (R = 1.341, X = 3684, Z = 3.92), zone 3: (R = 2,107, X = 5789, Z = 6.16). Methods used to determine the return value of the distance relay settings for securing network systems SUTT 150 kV GI Kapal-GI Pemecutan kelod is a method of Artificial Neural Network. Application of the method backpropagation Artificial Neural Network is used to determine the value of setting relays within the network system SUTT 150 kV GI Kapal-GI Pemecutan kelod obtained from the method of Artificial Neural Network is zone 1
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.