Use of Rogowski Coil as Current Transducer for Distance Relay Reach Correction

Abstract: Conventional iron core CT gets saturated with increase in system X/R ratio, burden connected across it under normal condition and presence of DC component in symmetrical current waveform under faulty condition. CT saturation causes distance relay (DR) to under reach and operate it with certain time delay. The problem becomes more critical when fault takes place near to the boundary of first zone of DR. RC has become more popular for measurement of normal and complex transient current due to its inherent linear… Show more