2021
DOI: 10.3390/en14216978
|View full text |Cite
|
Sign up to set email alerts
|

Thermal Calculations of Four-Row Plate-Fin and Tube Heat Exchanger Taking into Account Different Air-Side Correlations on Individual Rows of Tubes for Low Reynold Numbers

Abstract: Currently, when designing plate-fin and tube heat exchangers, only the average value of the heat transfer coefficient (HTC) is considered. However, each row of the heat exchanger (HEX) has different hydraulic–thermal characteristics. When the air velocity upstream of the HEX is lower than approximately 3 m/s, the exchanged heat flow rates at the first rows of tubes are higher than the average value for the entire HEX. The heat flow rate transferred in the first rows of tubes can reach up to 65% of the heat out… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
4
1

Citation Types

0
9
1

Year Published

2022
2022
2024
2024

Publication Types

Select...
3
2
1

Relationship

1
5

Authors

Journals

citations
Cited by 9 publications
(10 citation statements)
references
References 22 publications
0
9
1
Order By: Relevance
“…The relative difference between the Nusselt number presented in this study and the Nusselt number correlation for Wang et al [17], is 19.42 % for 𝑅𝑒 𝑑 𝑜 = 1000 and 30.42 % for 𝑅𝑒 𝑑 𝑜 = 13,000 (Figure 4a). The relative difference between the Nusselt number presented in this study and the Nusselt number correlation for Marcinkowski et al [16] is -3.6 % for 𝑅𝑒 𝑑 𝑜 = 3,000, 0.33 % for 𝑅𝑒 𝑑 𝑜 = 1,000 and -1.58 % for 𝑅𝑒 𝑑 𝑜 = 13,000 (Fig. 4a).…”
Section: Cfd Model Validationmentioning
confidence: 39%
See 4 more Smart Citations
“…The relative difference between the Nusselt number presented in this study and the Nusselt number correlation for Wang et al [17], is 19.42 % for 𝑅𝑒 𝑑 𝑜 = 1000 and 30.42 % for 𝑅𝑒 𝑑 𝑜 = 13,000 (Figure 4a). The relative difference between the Nusselt number presented in this study and the Nusselt number correlation for Marcinkowski et al [16] is -3.6 % for 𝑅𝑒 𝑑 𝑜 = 3,000, 0.33 % for 𝑅𝑒 𝑑 𝑜 = 1,000 and -1.58 % for 𝑅𝑒 𝑑 𝑜 = 13,000 (Fig. 4a).…”
Section: Cfd Model Validationmentioning
confidence: 39%
“…4 shows the air-side Nusselt and the air-side D-W friction factor as a function of Reynolds number. Figure 4a compares the correlations determined by the current study with Wang et al [18], Wang et al [17] and Marcinkowski et al [16] in case of Nusselt number comparison. Table 3 presents geometry dimensions of the compared studies.…”
Section: Cfd Model Validationmentioning
confidence: 55%
See 3 more Smart Citations