“…Corona inception voltage of the DC transmission lines related to many factors, including: pressure, temperature, humidity, etc., in addition to the environmental impact of external meteorology, the wire diameter, the surface roughness coefficient, the contamination condition, wire-to-ground height can also influence the Corona inception voltage [6][7][8][9][10][11][12][13][14][15][16].as altitude increases, the air pressure reduce,and the transmission line conductor corona inception voltage decreases [6,7].Therefore, the transmission lines which can safely operationed at low altitudes , may not be able to safe operation at high altitudes.The humidity also affects the important parameters of the transmission line corona characteristics, with increasing humidity, the transmission line conductor corona inception voltage decrease, the effect would be more significant when the pressure is low. [8][9][10][11][12][13].…”