The Influence of Harmonics on Error Stability of Energy Meter Verification Device and Its Suppression Measures

Abstract: .In view of the problem of poor error stability of the three-phase energy meter verification device under low current load, the working principle and error calculation method of the device are analyzed. The harmonics content and error data of the device under low current load before and after the installation of the isolation transformer are tested on site. And the role of the isolation transformer in suppressing the harmonics of the device is analyzed. From the harmonics content and error data of the output c… Show more