Study on decay‐like fracture of 500 kV composite insulators: Infrared, ultraviolet and electric field distribution detection

Abstract: The power outage caused by decay‐like fracture of composite insulators significantly impacts the power grid. In this paper, a decay‐like fractured insulator of 500 kV transmission line is taken as a research object. The detailed observation of core rod and silicone rubber housings, discharge results, temperature rises, and electric field distribution are obtained. (a) The fractured insulator has abnormal heating on the exposed core rod and sheath surface, and the ambient temperature and humidity significantly … Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
3
1
1

Citation Types

0
8
0

Year Published

2023
2023
2023
2023

Publication Types

Select...
6

Relationship

0
6

Authors

Journals

citations
Cited by 8 publications
(8 citation statements)
references
References 25 publications
0
8
0
Order By: Relevance
“…An experimental setup was prepared for the simulation of the surface discharge, which is minutely introduced in Ref. [ 24 ]. The GFRE sample was placed in a closed cavity with a pair of annular electrodes that were fixed at both ends of the rod.…”
Section: Materials and Methods Of Surface Discharge Testmentioning
confidence: 99%
See 1 more Smart Citation
“…An experimental setup was prepared for the simulation of the surface discharge, which is minutely introduced in Ref. [ 24 ]. The GFRE sample was placed in a closed cavity with a pair of annular electrodes that were fixed at both ends of the rod.…”
Section: Materials and Methods Of Surface Discharge Testmentioning
confidence: 99%
“…In addition, the “decay” characteristics shown in Figure 1 b suggest the severe degradation of the resin matrix, which cannot be the result of liquid immersion only. Hence, considering the abnormal temperature increase detected in actual operation, overheating is most likely another cause [ 23 , 24 ]. Moreover, because the overheating area is highly concentrated, it should be attributed to the current concentration or partial discharge instead of the overall temperature increase in the insulator [ 25 ].…”
Section: Introductionmentioning
confidence: 99%
“…(1) The sheath surface was black or had noticeable electrical erosion marks and even had electrical erosion holes; (2) The bonding strength of the core rod-sheath interface decreased and was even destroyed. (3) The surface color of the core rod gradually became black and even carbonized; (4) Filamentous fiber appears on the core rod surface, like decayed wood.…”
Section: Experimental Set-upmentioning
confidence: 99%
“…Composite insulators are increasingly used in the power grid and have become critical equipment in the transmission lines [1,2]. The reliability of the power grid is directly correlated with its performance.…”
Section: Introductionmentioning
confidence: 99%
“…There are various research methods for corona discharge characteristics of transmission lines, and generally the method of measurement is used. At present, the main measurement methods used include the following: direct observation of corona discharge with an ultraviolet imager [4][5][6], direct measurement of corona current on conductors [7][8][9], indirect measurement of various effects caused by corona discharge phenomenon, such as ionic electric field, radio interference etc. [10,11].…”
Section: Introductionmentioning
confidence: 99%