Status Report on the Water-Based NSTF RCCS Capability: Preparations and Design for the Transformation of the Natural Convection Shutdown Heat Removal Test Facility (NSTF) From Air to Water-based Cooling
Abstract:The following report provides an overview of the current status of the water-based transformation, including details of the design, geometry, and fabrication of the test section and network piping, for the ½ scale water-based NSTF program at Argonne National Laboratory.In early FY2015, efforts towards a water-based design began in parallel with on-going airbased work, and began by identifying top level objectives of the transformation. Scaling studies and preparation tasks with computational modeling were carr… Show more
“…As the intention of the NSTF throttling parametric testing is to provide generalizable data on blockages, K is the more meaningful value to report. In the case that CV is preferred by a user, Eq [4] provides a ready translation for any size valve.…”
Section: Valve Theorymentioning
confidence: 99%
“…These mean values over time of the raw coefficients are listed in Table 9. Through Eq [4] we can translate each value into the other and compare the calculations. The two values are consistent, as expected given that they rely on the same two data inputs of flow rate and DP.…”
Section: Char006: Static Inlet Port Separate Effects Testingmentioning
confidence: 99%
“…From here there are two options to translating to CV. We can either use Eq [4], as before, or modify Eq [1] with the determined valve K:…”
Section: Char006: Static Inlet Port Separate Effects Testingmentioning
confidence: 99%
“…After this, the inlet header valve position was varied according to Table 14. CV and K are calculated using Eqs [13] and [4]. (The assumed values for K = 0.048 at 0° are substituted for the fitted values, which overshoot this by roughly 1%.)…”
Section: Example Parametric: Dataquality083 Inlet Header Throttlingmentioning
“…As the intention of the NSTF throttling parametric testing is to provide generalizable data on blockages, K is the more meaningful value to report. In the case that CV is preferred by a user, Eq [4] provides a ready translation for any size valve.…”
Section: Valve Theorymentioning
confidence: 99%
“…These mean values over time of the raw coefficients are listed in Table 9. Through Eq [4] we can translate each value into the other and compare the calculations. The two values are consistent, as expected given that they rely on the same two data inputs of flow rate and DP.…”
Section: Char006: Static Inlet Port Separate Effects Testingmentioning
confidence: 99%
“…From here there are two options to translating to CV. We can either use Eq [4], as before, or modify Eq [1] with the determined valve K:…”
Section: Char006: Static Inlet Port Separate Effects Testingmentioning
confidence: 99%
“…After this, the inlet header valve position was varied according to Table 14. CV and K are calculated using Eqs [13] and [4]. (The assumed values for K = 0.048 at 0° are substituted for the fitted values, which overshoot this by roughly 1%.)…”
Section: Example Parametric: Dataquality083 Inlet Header Throttlingmentioning
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.