Rejuvenation of Retired Power Cables by Heat Treatment: Experimental Simulation in Lab

Abstract: In this work, heat treatment was performed on three retired 110 kV AC cables with service years of 0, 15 and 30, and the effects on the thermal and electrical performance of the cable insulation were investigated. First, each cable with a length approximately of 5 m was prepared and cut into five equal segments. Four segments of each cable were annealed at a temperature of 90, 95, 100, or 105 • C by building a small circuit to simulate cable operation. Then, a section at the middle of each segment was cut out,… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
3
1
1

Citation Types

0
11
0

Year Published

2020
2020
2023
2023

Publication Types

Select...
8

Relationship

4
4

Authors

Journals

citations
Cited by 10 publications
(11 citation statements)
references
References 23 publications
0
11
0
Order By: Relevance
“…H m is the enthalpy of fusion of an ideal polyethylene crystal per unit volume; and L is the lamellar thickness. The used values for calculation were as follows: H 0 f = 293 J/g, T m0 = 414, 6 K, H m = 2, 88 × 10 8 J/m 3 and σ e = 93 × 10 −3 J/m 2 .…”
Section: ) Results Of Dsc Measurementmentioning
confidence: 99%
See 2 more Smart Citations
“…H m is the enthalpy of fusion of an ideal polyethylene crystal per unit volume; and L is the lamellar thickness. The used values for calculation were as follows: H 0 f = 293 J/g, T m0 = 414, 6 K, H m = 2, 88 × 10 8 J/m 3 and σ e = 93 × 10 −3 J/m 2 .…”
Section: ) Results Of Dsc Measurementmentioning
confidence: 99%
“…Fourthly, the parameters of T 1 ' and T 2 ' in Figure 2 can be measured from the temperature recorder of the platform, and the parameter of P' was approximately equal to P 0 'due to R 0 ', P 1 ' and P 2 ' can be ignored comparing with P 0 '. Fifthly, the parameters of R 1 and ρ 1 at 50, 70 and 90 • C were derived from Formula (1) and (3).…”
Section: Diagnostic Measurements Of Xlpe Thermal Parametersmentioning
confidence: 99%
See 1 more Smart Citation
“…To detect the cable insulation condition, the commonly used methods include 50Hz dielectric loss, leakage current, partial discharge, etc. [9]- [13]. These methods have been widely recognized in actual cable detection, but there are still shortcomings.…”
Section: Introductionmentioning
confidence: 99%
“…In the contact thermometry, the temperature sensor is installed directly on the conductor surface. This thermometry also has high measuring precision and anti-interference capability [23,24]. However, as the sensor is in direct contact with the conductor, it is difficult in terms of sensor maintenance [25].…”
Section: Introductionmentioning
confidence: 99%