Pole-to-Ground Fault Analysis and Fast Protection Scheme for HVDC Based on Overhead Transmission Lines

Abstract: Flexible direct current (DC) transmission network technology is an effective method for large capacity clean energy access to power grids, but the DC short-circuit fault detection for it is a difficult problem. In this paper, the pole-to-ground fault transient characteristics in a multi-terminal DC power grid, based on overhead transmission lines and DC circuit breakers, are analyzed firstly. Then, a fast protection scheme is proposed according to the fault transient characteristics. Only local information is … Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1
1

Citation Types

0
21
0

Year Published

2017
2017
2024
2024

Publication Types

Select...
8

Relationship

0
8

Authors

Journals

citations
Cited by 32 publications
(21 citation statements)
references
References 24 publications
(22 reference statements)
0
21
0
Order By: Relevance
“…Constraint (43) can be analyzed using the arm current Equations (24) and (25) in Section 2. Setting R FCL = 20 Ω, the L FCL_min is calculated as 219 mH to satisfy Constraint (43). The arm currents are compared under the calculated L FCL_min and L FCL_min obtained via a simulation ( Table 3).…”
Section: Parametric Designmentioning
confidence: 99%
See 2 more Smart Citations
“…Constraint (43) can be analyzed using the arm current Equations (24) and (25) in Section 2. Setting R FCL = 20 Ω, the L FCL_min is calculated as 219 mH to satisfy Constraint (43). The arm currents are compared under the calculated L FCL_min and L FCL_min obtained via a simulation ( Table 3).…”
Section: Parametric Designmentioning
confidence: 99%
“…Considering that the resistance value of a 2 mH reactor equals 18.9 mΩ [42], the power loss is expressed as Equation (49). where is the rated DC line current, = 0.00945 Ω/mH is based on Reference [43], is the smoothing reactor, and is the rated DC line power. Thus, the smoothing reactor in the proposed scheme causes 0.135% power loss in comparison with the rated DC line power, thus denoting a promising economic efficiency.…”
Section: Influence On Fault Currentmentioning
confidence: 99%
See 1 more Smart Citation
“…The article concerns the analysis of processes and the operation of hybrid switches [1,2] related to the arcless switching off of short-circuit currents in power circuits operating in difficult environmental conditions [3,4]. In the conditions under consideration, the main cause of disruption of the power system operation is a dynamic short circuit, but one cannot omit such factors as vibrations, lightning, or changing weather conditions.…”
Section: Introductionmentioning
confidence: 99%
“…The traditional fault location is based on the line protection action. Numerous methods have been proposed for transmission line protection [1], with no consideration of the exact fault location, causing the need for time-consuming line patrols. It is necessary to find the exact fault location in transmission lines.…”
Section: Introductionmentioning
confidence: 99%